Same P1/P2 for all three cases. For a pump system where ΔP falls as flow rises, size the maximum case with its own (lower) ΔP.
Rule of thumb: equal-% valves about 15–20 % open at minimum flow, ~75 % at normal and at most 90–95 % at maximum. Linear trims: keep all cases between 15 % and 95 % of rated Cv.
| Temperature | Equal % |
| Liquid pressure | Equal % |
| Gas pressure, small volume | Equal % |
| Gas pressure, large volume | Linear if valve ΔP stays > 20 % of system ΔP |
| Flow and level | Linear if valve ΔP at max flow > 20 % of ΔP at min flow; else equal % |
| On/off, relief, surge | Quick opening |
Valve factors and rated Cv values are typical for each style, not a specific product. Confirm final selection with the manufacturer's data and sizing software, and check noise (IEC 60534-8) separately.