Devices & Valves / Animations / 4–20 mA current loop
4–20 mA Current Loop
Change the process pressure and watch the loop current, the voltage at the I/O card and the DCS reading. Then break the wire or fail the sensor to see how the DCS detects faults.
- Loop current
- 12.00 mA
- Voltage at AI card
- 3.00 V
- % of range
- 50.0 %
- DCS reading
- 5.00 bar
- Signal status
- Normal
Status follows NAMUR NE 43: ≤ 3.6 mA or ≥ 21 mA is a fault; 3.8–20.5 mA is the valid measuring range.
What you are seeing
- The 24 V supply, the transmitter and the 250 Ω resistor are in series, so the same current flows through all of them. The moving dots show that current.
- The transmitter sets the current: 4 mA at 0 % of range and 20 mA at 100 %. The I/O card measures the voltage across the 250 Ω resistor: 1 V to 5 V.
- Because the bottom of the range is 4 mA, not 0 mA (a "live zero"), a broken wire (0 mA) can't be mistaken for a real zero reading.
- A healthy transmitter that detects an internal fault drives its output to ≤ 3.6 mA or ≥ 21 mA (NAMUR NE 43), so the DCS can flag the reading as bad.
Work out your own values with the Analog Signal Scaler, or read Transmitters & Signals.