Control Systems / P&ID symbols & tags

P&ID Symbols & Instrument Tags

Every instrument on a piping and instrumentation diagram (P&ID) is a circle with letters and a number. Once you can read those letters, the bubble shape and the lines between them, a P&ID tells you exactly how a plant is measured and controlled.

This page follows the widely used ISA-5.1 conventions in general terms. Projects often add their own rules in a symbols legend sheet: always check the legend of the drawing set you are using.

Reading a tag number

A tag such as FIC-101 has two parts:

  • Letters (functional identification): the first letter is the measured or initiating variable; the following letters say what the instrument does.
  • Number (loop number): every instrument in the same loop shares it, e.g. FT-101, FIC-101 and FV-101 are one flow loop. Many projects prefix the area or unit, e.g. 21-FIC-101.

So FIC-101 = Flow · Indicating · Controller in loop 101.

Common letter codes

First letterMeasured variable
AAnalysis (pH, O₂, gas…)
FFlow
LLevel
PPressure
PD / dPPressure differential
TTemperature
SSpeed / frequency
VVibration
ZPosition
HHand (manual)
XUnclassified (see legend)
WWeight / force
Following letterFunction
TTransmitter
IIndicator
CController
RRecorder
EPrimary element (sensor)
GGauge / glass
VValve, damper
YRelay / compute / converter (e.g. I/P)
SSwitch
AAlarm (with H/L: high/low)
QTotalise (2nd letter)
ZSafety / emergency action (e.g. SDV, XV)

Examples: LT level transmitter · TE temperature element · PSH pressure switch high · FQI flow totaliser · PDT differential pressure transmitter · TY temperature converter · LAHH level alarm high-high.

Tag decoder

Type a tag to see what it means:

Bubble types: where is the instrument?

PITICPYFICXS Field mountedMain control roompanel (accessible)Behind panel /not accessible DCS / shareddisplay & controlPLC logic A double line instead of a single line means a local (auxiliary) panel.
The outline tells you where the function lives and whether the operator can access it.

Signal lines

Process line (pipe)Electrical signal (e.g. 4–20 mA)Pneumatic signal (instrument air)Data link / fieldbus (software signal)Capillary tube (filled system)
Common line types. Projects may use slight variations: check the legend sheet.

Valve symbols

  • Control valve: two triangles tip-to-tip (a "bow tie") with an actuator on top: a dome for a diaphragm actuator, a box for a piston.
  • Fail action is written beside it: FC fail closed, FO fail open, FL fail last (locked).
  • Shutdown / on-off valves are usually tagged SDV, ESDV, XV or BDV (blowdown), with a solenoid "S" box on the actuator.
  • Relief valves (PSV) show an angle body with a spring.

A worked loop: flow control

FE-101 FT101 FIC101 FY101 FV-101FC
FE-101 (orifice) → FT-101 (DP transmitter, field) → FIC-101 (controller in the DCS) → FY-101 (I/P converter) → FV-101 (control valve, fail closed). Same loop number throughout.

Reading it out loud: "Flow element 101 is measured by field transmitter FT-101, sent electrically to the DCS controller FIC-101, whose output goes to the I/P converter FY-101 and pneumatically to control valve FV-101, which fails closed."

Q&A: test yourself

Related: Control Systems · Control Valves · SIS & SIL Basics