Measurement / Flow / Animated

How Flow Meters Work

Move the flow slider and watch five measuring principles respond: the flow pattern in the pipe, an orifice plate, a turbine meter, a magnetic meter and a vortex meter.

50 % of max Pipe 100 mm. 100 % = 3 m/s.

1. Laminar or turbulent: the Reynolds number

How a fluid moves in a pipe depends on the balance between its momentum (which keeps it moving) and its viscosity (which smooths it out). That balance is the Reynolds number, a number without units:

Re = ρ · v · D / μ (density × velocity × pipe diameter ÷ viscosity)

Below about 2300 the flow is laminar: smooth layers, fastest in the centre, a pointed (parabolic) velocity profile. Above about 4000 it is turbulent: eddies mix the flow and the profile becomes flat. In between is a transition zone. Most meters are calibrated for turbulent flow, so very slow or very viscous flows can read wrongly. Try a thick oil to see laminar flow.

Fluid Velocity Re Regime

2. Orifice plate: flow from differential pressure

A plate with a smaller hole forces the fluid to speed up. Faster fluid has lower pressure (Bernoulli), so a differential pressure (DP) appears across the plate. DP grows with the square of flow: double the flow and DP rises four times.

Q = K · √ΔP ΔP ∝ Q²

That is why the DP transmitter's signal must be square-rooted (in the transmitter or the DCS, never both) to read flow. It also explains the limited turndown: at 10 % flow the DP is only 1 % of span, lost in the noise.

Flow DP DP signal (linear in DP) After square root

3. Turbine meter: counting revolutions

The flow turns a bladed rotor. Its speed is proportional to the fluid velocity, so each blade passing a pick-up coil is a known volume. The pulses per unit volume are the meter's K-factor; flow = pulse frequency ÷ K-factor. Turbines are accurate on clean, steady liquids, but bearings wear and viscosity changes shift the K-factor.

K-factor 50 pulses/LFlow Pulse frequency

4. Magnetic meter: Faraday's law

Coils create a magnetic field across the pipe. A conductive liquid moving through it acts like a moving wire, and a voltage appears between two electrodes, proportional to the average velocity:

E = k · B · D · v (field strength × pipe diameter × velocity)

No moving parts and no pressure loss, and it handles slurries well. But the liquid must conduct electricity (typically above about 5 µS/cm), so it can't measure oil, gas or very pure water. The pipe must run full.

Velocity Electrode voltage

5. Vortex meter: counting eddies

A bluff body (a "shedder bar") across the pipe sheds vortices alternately from each side, like a flag flapping in the wind. The shedding frequency is proportional to velocity:

f = St · v / d (Strouhal number × velocity ÷ bar width)

The Strouhal number stays nearly constant over a wide range of Reynolds numbers, so the meter is linear without needing density or viscosity. Below a minimum velocity, vortices stop forming and the meter reads zero (a low-flow cut-off). It needs a straight run of pipe upstream.

Velocity Shedding frequency

Choosing a flow meter

NeedGood choicesWatch out for
Low cost, any clean fluid, standards-basedOrifice / venturi (DP)Pressure loss, square-root, ~4:1 turndown, straight runs
Conductive liquids, slurries, no pressure lossMagneticConductivity, pipe must be full, grounding
Steam, gas and clean liquids, wide rangeVortexLow-flow cut-off, vibration, straight runs
Mass flow, custody transfer, density tooCoriolisCost and size on large lines, gas bubbles
Clean, steady liquids, high accuracyTurbineBearing wear, viscosity changes, debris
Large pipes, no pipe cuttingClamp-on ultrasonicPipe condition, bubbles and solids

Also check: required accuracy and turndown, pressure loss allowed, hazardous-area rating, upstream/downstream straight runs, and how the meter will be calibrated. More detail in Flow measurement; check a DP range with the Square Root Extraction app.

Teaching animations, not to scale. Formulas show the principle; real meters use calibration factors and standards (for example ISO 5167 for orifice plates).