Equipment
- Pressure source: hand pump (pneumatic up to ~40 bar, hydraulic above), or a dead-weight tester for the highest accuracy.
- Reference gauge or calibrator with a valid calibration certificate. It should be at least 4 times more accurate than the instrument under test (a 4:1 test uncertainty ratio).
- mA meter (usually inside a documenting calibrator) and a 24 V loop supply.
- HART communicator for smart transmitters (to read the PV and to trim).
- Hoses and fittings rated for the test pressure, and the right fluid: never use oil-filled equipment on oxygen service.
Set-up
- Isolate the transmitter from the process (manifold sequence for DP: see DP Transmitters), vent, and drain if liquid-filled.
- Connect the pump, reference and transmitter; leak-test at the top pressure (the reading must hold steady).
- For DP transmitters, apply pressure to the H side with L vented to atmosphere.
- Mount the transmitter in its normal orientation, or zero it after mounting: position affects the zero.
- Exercise the instrument: go to 100 % and back once before recording.
The 5-point up/down test
Apply 0, 25, 50, 75 and 100 % of the calibrated range rising, then 75, 50, 25, 0 % falling. Approach each point from one direction only (don't overshoot and come back), and let the reading settle.
| % | Applied (0–10 bar) | Expected mA | Rising mA | Falling mA | Error % span |
|---|---|---|---|---|---|
| 0 | 0.000 | 4.000 | 4.012 | 4.016 | +0.10 |
| 25 | 2.500 | 8.000 | 8.010 | 8.020 | +0.13 |
| 50 | 5.000 | 12.000 | 12.008 | 12.018 | +0.11 |
| 75 | 7.500 | 16.000 | 16.006 | 16.014 | +0.09 |
| 100 | 10.000 | 20.000 | 20.004 | – | +0.03 |
The difference between rising and falling readings at the same point is hysteresis. This example passes a ±0.25 % tolerance.
Calculating the error
Error (% of span) = (measured mA − expected mA) / 16 mA × 100
Try it:
Compare the worst error against the tolerance on the calibration sheet (often ±0.25 % or ±0.5 % of span; check your site's standard). Expected currents for any range: 4–20 mA Signal Scaler.
Adjusting: which trim?
- Re-range (LRV/URV) changes what pressure the 4 and 20 mA represent. It is a configuration change, not a calibration. See Transmitter Re-range.
- Sensor trim (zero and span, also called lower/upper sensor trim) corrects the digital pressure reading against your reference. Do it when the HART PV is wrong.
- Analog output (D/A) trim corrects the 4 and 20 mA output against your meter. Do it when the PV is right but the mA is off.
- Zero trim at line pressure (DP) removes static-pressure and mounting offsets after installation.
After any adjustment, repeat the full 5-point test and record both as-found and as-left results.
Pressure switches: set point, reset and deadband
- Connect a continuity tester or meter across the contacts (NO or NC as used in service).
- Raise the pressure slowly near the set point and record when the contact changes.
- Lower slowly and record the reset point. Deadband = set − reset (for a high switch).
- Adjust the set point screw if needed and repeat three times for repeatability.
- For a low switch, the set point is on falling pressure and it resets on rising.
Records
A calibration certificate or sheet should show: tag, serial, range, tolerance, reference equipment and its certificate number and due date, as-found and as-left data, pass/fail, date, technician and next due date. A documenting calibrator can store and upload these automatically.
Q&A: test yourself
Related: Pressure Measurement · DP Transmitters · Loop Checking