Radar vs Guided-Wave Radar Level

Radar has become the default level technology in many plants. There are two families: non-contact radar that beams through the air, and guided-wave radar (GWR) that sends its pulse down a probe. Here is how they work and how to pick and install the right one.

Go deeper: Radar Level Lab: interactive GWR (5300) and non-contacting radar (5408) simulations, interface echoes, commissioning, troubleshooting tree and a fault lab.

How both work: time of flight

The gauge sends a microwave signal down to the surface and measures how long the reflection takes to return. Microwaves travel at the speed of light, so the time is tiny (nanoseconds), but the electronics measure it precisely:

distance = (c × t) / 2 level = reference height − distance

Because it measures distance with microwaves, radar is almost unaffected by density, pressure, temperature, vapour or dust changes that upset DP or ultrasonic gauges.

Side by side

Non-contact radar echo from surface beam through the air, no contact Guided-wave radar (GWR) pulse alongthe probe probe (rod, cable or coax) in the product
Both measure the time for the microwave to reach the surface and return; GWR guides the energy along a probe, so much more of it comes back.

Dielectric constant (DK, εr): why it matters

The strength of the reflection depends on the product's dielectric constant. Water and acids (DK ≈ 80) reflect strongly; oils and hydrocarbons (DK ≈ 2) reflect weakly; LPG and some powders are even lower.

  • Low DK = weak echo. GWR handles low DK much better because the probe concentrates the energy.
  • For interface (oil on water), GWR can see both the top surface and the oil/water interface, as long as the upper layer has a low DK and the lower one a high DK, with a clear boundary.

Which one to choose

Non-contact radarGuided-wave radar
Contact with productNoneProbe immersed
Low DK productsHarder (needs high frequency, good set-up)Very good
Interface measurementNoYes
Foam, turbulence, condensationCan lose the echoMore robust
Sticky, coating, fibrous productGood (no contact)Build-up on probe can cause errors
Tall tanks, agitatorsGood (no probe to break)Long probes; agitators can damage them
Small nozzles, internals80 GHz narrow beam helpsNot affected by internals

Frequency: modern non-contact radars use about 80 GHz for a narrow beam that avoids nozzles and internals; older 6–26 GHz units have wider beams.

Installation rules

  • Non-contact: keep the beam clear of ladders, agitators, fill streams and the tank wall; avoid the centre of dome roofs (focused echoes). The antenna should extend past the nozzle end.
  • GWR: keep the probe away from the wall and internals by the distance the manufacturer gives; anchor or weight long cable probes; use a coaxial probe in small chambers or very low DK.
  • In a bridle or stilling well, size and smooth it as the manufacturer specifies; a GWR in a chamber is a common replacement for displacers.
  • Check the blocking (dead) distance at the top: the gauge can't measure very close to its own flange.

Set-up and false echoes

  1. Enter the reference height (from flange to tank bottom) and the measuring range carefully. Most level errors are a wrong reference.
  2. With the tank empty or low, run a false echo mapping (interference suppression) so the gauge learns and ignores fixed obstacles.
  3. Check the echo curve with the configuration software: you should see one clear surface peak above the threshold.
  4. Compare against a manual dip or gauge glass at two levels and adjust the offset, not the range.

Echo curves are viewed with the manufacturer's DTM: see DTM & device software.

Troubleshooting

SymptomLikely cause
Level stuck at a fixed valueLocked on a false echo (internal, nozzle); redo mapping
Reads full when emptyAntenna fouled or condensation; ringing in the nozzle
Echo lost (fault current)Foam, heavy turbulence, low DK product, coating
Constant offset vs dipWrong reference height or offset
GWR reads high near the bottomProbe end/weight echo, build-up on the probe
Interface wrongEmulsion layer, wrong upper-layer DK entered