Pressure Measurement

Pressure is the foundation of flow and level measurement too. Get the references, units and installation right and half your instrument problems disappear.

Gauge, absolute and differential

  • Gauge (g): relative to the local atmosphere. A tyre gauge reads 0 at sea level and at the top of a mountain.
  • Absolute (a): relative to perfect vacuum. Needed for vacuum services, vapour pressure, gas density calculations and steam tables.
  • Differential (d): the difference between two points. Used for flow, level, filter and pump monitoring.
P_abs = P_gauge + P_atm (P_atm ≈ 1.01325 bar at sea level)
Valve sizing formulas and gas calculations use absolute pressure. Mixing up bar(g) and bar(a) is one of the most common calculation errors.

Units you'll meet

UnitEquals
1 bar100 kPa = 14.504 psi = 1.0197 kg/cm² = 10 197 mmH₂O
1 psi6.8948 kPa = 68.948 mbar = 27.68 inH₂O
1 mmH₂O9.80665 Pa (water at 4 °C)
1 inH₂O249.09 Pa (at 4 °C; some standards use 20 °C or 60 °F)
1 atm101.325 kPa = 760 mmHg = 760 torr

Convert any of these with the Unit Converter.

Pressure gauges

Most local gauges use a Bourdon tube (a curved tube that straightens under pressure); low ranges use diaphragms or capsules. Good practice:

  • Select the range so that normal operating pressure sits at about 50–75 % of full scale.
  • Use liquid-filled gauges on vibrating or pulsating services, plus a snubber on pump discharges.
  • Use a siphon (pigtail) on steam, so condensate protects the element from live steam.
  • Use a solid-front, blow-out-back case for safety on high-pressure gas.

Pressure transmitters

Smart transmitters use capacitive, piezoresistive or resonant sensors and output 4–20 mA with HART, or a fieldbus. Key specification points:

  • URL vs calibrated range: a sensor with URL 100 bar can be ranged 0–10 bar (10:1 turndown), but accuracy worsens at high turndown. Check the vendor's formula.
  • Overpressure and static pressure limits, especially for DP cells in high-pressure lines.
  • Wetted materials (316L, Hastelloy, Monel, tantalum) and fill fluid for the process chemistry.
  • Hazardous-area certification (Ex d / Ex ia) to match the area classification.

Diaphragm (remote) seals

A seal isolates the transmitter from process fluids that are corrosive, viscous, crystallising, very hot or sanitary. A capillary filled with fill fluid transmits the pressure. The trade-offs are slower response and temperature errors from the fill fluid. Keep capillaries as short as possible, protected from the sun, and of equal length on both sides of a DP cell (a balanced system).

Valve manifolds

A 2-valve manifold (block and vent) serves gauge pressure transmitters. DP transmitters use 3-valve (two blocks plus an equaliser) or 5-valve (adds two vents) manifolds.

Typical sequence: putting a DP transmitter into service

  1. Check that all valves are closed, then open the equalising valve.
  2. Slowly open the HP block valve. Both sides are now pressurised equally, so the cell sees no overload.
  3. Close the equalising valve.
  4. Slowly open the LP block valve.

To take it out of service, reverse the order: close LP, open the equaliser, close HP, then vent. With the equaliser open and both blocks closed, the transmitter should read zero DP, which is a quick zero check.

Never open the equaliser while both block valves are open on a live line: it bypasses the primary element and, on a DP flow meter with a wet leg or seal pot, it can drain the legs. Always follow your site's procedure and permit system.

Installation tips

  • Liquids: transmitter below the tap, so gas bubbles rise back to the process.
  • Gases: transmitter above the tap, so condensate drains back.
  • Steam: transmitter below the tap with filled legs (condensate), so hot steam never reaches the sensor.
  • Slope impulse lines at least 1:12 (about 8 %), avoid loops that trap gas or liquid, and keep both legs of a DP pair at the same temperature.
  • Heat-trace lines that can freeze or solidify, but don't overheat transmitters beyond their limits.