RTD vs Thermocouple

The two sensors behind almost every plant temperature reading. Here is how each one works, when to use which, how to wire them so they read right, and how to find the fault when they don't.

How they work

RTD (resistance temperature detector)

A fine platinum wire or film whose resistance rises with temperature. A Pt100 is 100 Ω at 0 °C and about 138.5 Ω at 100 °C (α = 0.00385). The transmitter passes a small current and measures the resistance.

Thermocouple (TC)

Two different metals joined at the hot end. The junction creates a small voltage (millivolts) that depends on the difference between the hot junction and the cold end where the wires meet copper. Type K gives about 41 µV/°C.

Convert either one in the app: RTD Converter · Thermocouple Converter.

Which one to choose

RTD (Pt100)Thermocouple
Typical range−200 to about 600 °C−200 to 1700+ °C, depending on type
AccuracyBetter: Class A ±(0.15 + 0.002·|t|) °CLower: type K class 1 about ±1.5 °C or 0.4 %
Stability / driftVery stableDrifts more, especially at high temperature
ResponseSlower (larger element)Faster (tiny junction)
VibrationWire-wound can be fragile; thin film is betterRugged
WiringOrdinary copper, 3- or 4-wireMatching extension/compensating cable
CostHigher sensor costLower sensor cost

Rule of thumb: use an RTD for accuracy below about 500–600 °C (process control, custody transfer, bearings). Use a thermocouple for high temperatures (furnaces, heaters, exhaust, flue gas) or where fast response and ruggedness matter more than accuracy.

RTD wiring: 2, 3 and 4 wire

2-wire3-wire4-wire lead resistance adds tothe reading (error) 3rd wire cancels leadresistance (industry standard) separate current and sensepairs: most accurate
Each 1 Ω of uncompensated lead resistance adds about 2.6 °C to a Pt100 reading, which is why 2-wire is avoided on long runs.

Best practice: mount a head-mounted transmitter on the sensor and send 4–20 mA back to the control room. The short RTD leads then don't matter, and the signal is immune to lead resistance and noise.

Thermocouple types and cable

TypeMetalsApprox. rangeTypical use
KChromel / Alumel−200 to 1250 °CGeneral purpose, most common
JIron / Constantan0 to 750 °COlder plants, reducing atmospheres
TCopper / Constantan−200 to 350 °CLow temperature, cryogenic
NNicrosil / Nisil−200 to 1250 °CMore stable alternative to K
EChromel / Constantan−200 to 900 °CHighest output (mV/°C)
R, S, BPlatinum / Rhodiumup to 1600–1700 °CFurnaces, glass, very high temperature
  • Between the TC head and the transmitter, use matching extension or compensating cable of the same type. Plain copper creates a new junction and a large error.
  • Watch the polarity: reversing the wires makes the reading go the wrong way as temperature rises.
  • Colour codes differ between standards (IEC 60584 vs ANSI). Check which one your project uses before trusting colours.

Cold-junction compensation

A thermocouple measures the difference between its hot junction and the point where it connects to the copper terminals (the cold junction). The transmitter or input card measures the terminal temperature and adds it back:

mV(hot) = mV(measured) + mV(cold-junction temperature) → convert to °C

That is why you cannot just read the mV with a multimeter and look it up in a table without correcting for terminal temperature. A calibrator in "TC simulate" mode handles this automatically.

Thermowells and response time

  • A thermowell protects the sensor and lets it be removed without opening the process. It also slows the response (often 30 s to minutes).
  • Spring-loaded sensors pressed to the bottom of the well, and a well bore matched to the sensor, speed up response.
  • Long wells in fast flow can vibrate and break: they need a wake-frequency calculation (ASME PTC 19.3 TW).
  • Insertion length: typically the tip in the middle third of the pipe, and at least about 10 sensor diameters immersion to avoid stem conduction errors.

Troubleshooting

SymptomLikely cause
RTD reads very high / over-rangeOpen circuit (broken element or loose terminal)
RTD reads very low / under-rangeShort circuit, moisture in the head
RTD reads a few °C high, steady2-wire connection or unbalanced 3-wire leads
TC reads near ambient while process is hotCopper cable used instead of extension cable, or a shorted junction near the head
TC reading falls as process heatsReversed polarity
TC reading wrong by a constant offsetWrong TC type configured, or cold-junction compensation off
Noisy, jumping readingGrounded junction plus earth loop, cable near VFD/power cables
Slow to respondSensor not touching the thermowell bottom, oversized well

Quick check: disconnect the RTD and measure it with a multimeter (≈ 100 Ω at 0 °C, ≈ 108 Ω at 20 °C). For a TC, check continuity (a few ohms) and insulation to earth.